Safety and emc standards, Compliance with safety and emc standards – Yokogawa PR300 Power and Energy Meter User Manual

Page 64

Advertising
background image

Appendix

A-7

IM 77C01E01-01E

1

2

3

4

5

A

Appendix 1 Specifications of PR300

Insulation resistance Between each of the voltage input, current input, power, ground, digital input, pulse output,

analog output, RS-485 communication output, Ethernet communication output, and alarm
output terminals: 100 M

⍀ minimum (at 500 V DC)

Withstand voltage

Between each of the voltage input, current input, power, and ground terminals: 2500 V AC for 1
minute

Between (the voltage input, current input, power, and ground terminals) and the digital input,
pulse output, analog output, alarm output, RS-485 communication output, and Ethernet
communication output terminals: 2500 V AC for 1 minute

Between each of the digital intput, pulse output, analog output, alarm output, and (RS-485
communication output, Ethernet communication output) terminals: 1000 V AC for 1 minute

Between the RS-485 communication output and Ethernet communication output terminals: 500 V
AC for 1 minute

Impulse withstand voltage

Between all of the voltage input, current input, and power terminals and the ground terminal
Between all of the output and ground terminals and all of the voltage and current input terminals:
6 kV (1.2/50

µs), 10 times for positive and negative

Effects of magnetic field 400 A/m or less Active power:

±0.5% of F.S., Voltage: ±0.25% of F.S.

Effects of changes in ambient temperature

±0.03%/°C for a temperature change rate of 10°C/h or less (when 0.05In Ϲ I Ϲ Imax and power factor = 1)

±0.05%/°C for a temperature change rate of 10°C/h or less (when 0.1In Ϲ I Ϲ Imax and power factor = LAG0.5)
In: rated current; I: present current input

Effects of power supply voltage variations

Active power:

±0.25%, Voltage/Current: ±0.125%

(for variations within the power supply operating range (when 0.01In and power factor = 1))
In: rated current

Effects of input frequency

Active power:

±0.25%, Voltage/Current: ±0.125% (for variations of 45 to 65 Hz)

Power supply

100 - 240 V AC

Ϯ10% (50/60 Hz) or 130 - 300 V DC Ϯ15%

Power consumption

AC drive

10 VA maximum

DC drive

5 W maximum

Safety and EMC Standards

Safety standards

Compliant with
IEC/EN61010-1
UL61010-1
CAN/CSA C22.2 No.61010-1-04 (C-UL Listed)

Measurement category: 600V CAT.III

Measurement

category

CAT.I

CAT.II

CAT.III

CAT.IV

Descriptions

Circuits not directly connected to the main power
supply

Circuits directly connected to low-voltage facility

Circuits in building facility

Power sources for low-voltage facility

Remarks

House-use equipment, portable
tools, etc.

Switchboards, circuit breakers, etc.

Overhead lines, cable systems, etc.

Mains supply installation category: CAT.II
Pollution degree: 2 (IEC/EN61010-1)

Rated measurement input
Voltage input: 600 V AC (between terminals)
Current input: 600 V AC (across ground)

EMC-compliant standard

Compliant with EN61326
During testing, the instrument continues to operate at a measurement accuracy within

Ϯ20%.