Demand alarm, Example demand measurement, Demand alarm mask time – Yokogawa PR300 Power and Energy Meter User Manual

Page 55: Demand alarm release function, Measurement example, Demand alarm -14 example demand measurement -14

Advertising
background image

4-14

IM 77C01E01-01E

4.7

Demand Measurement (Optional Measuring Function)

Demand Alarm

Demand alarm output

Function:

When the set demand alarm point is exceeded, an alarm is output.

Output signal:

Open collector

Output capacity: 30 V DC, 200 mA

Demand alarm release function

Automatic release: When the demand value falls below the demand alarm point, the alarm is canceled.
Manual release:

The state of the alarm is maintained even if the demand value falls below the

demand alarm point. It is canceled via communication or by digital input or the
operation key.

Digital input

Number of inputs:

1

ON signal:

4.5 to 25 V DC

OFF signal:

within

Ϯ1 V DC

Demand alarm mask time

The demand alarm mask time is the time between the beginning of the demand period and the set time,
during which a demand alarm is not recognized.

Example Demand Measurement

0

10

20

32

30

100

200

300

400

500

(kW)

Demand period:

10 minutes

Demand period:

10 minutes

Demand period:

10 minutes

Demand measuring time: 32 minutes

(update interval: 10 seconds, times of measurement: 192)

Demand power

Demand alarm point

Demand alarm
mask time

Time (min)

Active power (kW)

Active energy (kWh)

Does not turn on
in the demand
alarm mask time.

turns on

during the
demand alarm.

Maximum demand value

Demand alarm output (open collector)

In conjunction with the demand alarm lamp, the
demand alarm output keeps sending an alarm until cancellation.

To manually cancel
the alarm,

press once or perform the
cancellation procedure via communication.

The alarm can be canceled by the operation key
or via communication regardless of the status
of the start/stop operation.

When the demand
alarm release function
is set to “Automatic
release,” the alarm is
automatically canceled
when the demand value
falls below the alarm
point.

Maximum demand value

The maximum demand value is the maximum value in the demand measuring time. This value is retained
until system reset or start of the next demand measurement.