Battery Management System events

Code

Severity

Description

0x0801

Informational

System: Communication established.

0x0802

Severe

System: Communication lost.

0x080D

Informational

System: Configuration has been changed.

0x080E

Severe

Charger: String voltage is low.

0x080F

Informational

Charger: Low string voltage returned to normal.

0x0810

Severe

Charger: String voltage is high.

0x0811

Informational

Charger: High string voltage returned to normal.

0x0812

Warning

Charger: High ripple current.

0x0813

Informational

Charger: High ripple current returned to normal.

0x0814

Severe

Charger: String discharging. See

Discharge cycle counter

.

0x0815

Informational

Charger: String no longer discharging.

0x0816

Severe

Battery: Cell shorted.

0x0817

Informational

Battery: Cell short cleared.

0x0818

Warning

Management Controller: Open fuse or connection.

0x0819

Informational

Management Controller: Open fuse or connection normal.

0x081A

Severe

Battery: Capacity is low.

0x081B

Informational

Battery: Low capacity is now normal.

0x081C

Warning

Battery: Ohmic value is high.

0x081D

Informational

Battery: High ohmic value is now normal.

0x081E

Severe

Battery: Thermal runaway in progress.

0x081F

Informational

Battery: Thermal runaway no longer in progress.

0x0820

Warning

Battery: Dryout/sulfation present.