Snmp, User’s guide, Battery management system – APC Battery Management System User Manual

Page 54

Advertising
background image

®

USER’S GUIDE

Battery Management System

47

SNMP

An

Access

option (

Settings

in the control console) enables (by default) or

disables SNMP. When SNMP is enabled, the

Access Control

settings

allow you to control how each of the four available SNMP channels is used.

To define up to four NMSs as trap receivers, see

Trap Receivers

;

to use SNMP to manage a UPS or an environmental monitor, see
the PowerNet

®

SNMP Management Information Base (MIB)

Reference Guide (

.\doc\en\mibguide.pdf

) on the APC Battery

Management System Utility CD.

Setting

Definition

Community
Name

This setting defines the password (maximum of 15 characters) which an
NMS that is defined by the

NMS IP

setting uses to access the channel.

NMS IP/
Domain
Name

Limits access to the NMS specified by a domain name or to the NMSs
specified by the format used for the IP address:

• A domain name allows only the NMS at that location to have access.
• 159.215.12.1 allows only the NMS with that IP address to have access.
• 159.215.12.255 allows access for any NMS on the 159.215.12 segment.
• 159.215.255.255 allows access for any NMS on the 159.215 segment.
• 159.255.255.255 allows access for any NMS on the 159 segment.
• 0.0.0.0 or 255.255.255.255 allows access for any NMS.

Advertising