Alarms, Fault alarm criteria, User’s guide – APC Battery Management System User Manual

Page 176: Battery management system

Advertising
background image

®

USER’S GUIDE

Battery Management System

169

Alarms

Fault Alarm Criteria

Fault

LED

Fault Criteria

Charger Voltage Low

Charger

Less than 2.1 volts per cell for lead-acid
batteries, or as set by user.

Charger Voltage High

Charger

Greater than 2.4 volts per cell for lead-acid
batteries or as set by user.

Shorted Cell

Batteries

Less than ((#Cells/Batt)-1) x (Vstring)

(#Cells/Batt) x (#Batt/String)

Blown Fuse/Open
Connections or Wiring

Management
Controller

Less than ½ volt on first or last battery in a
string or two consecutive batteries within a
string.

Low Capacity

Batteries

Any individual battery with more than 20%
lower voltage than the highest battery in
the same string during a discharge.

Thermal Runaway

Batteries

Greater than 20% more response current
than the benchmark, or greater than 95º F
battery temperature, or as set by the user.

Dryout/Sulfation/Opens

Batteries

Greater than 20% less response current
than benchmark, or as set by user.

High or Low Operating
Temperature

Environment

Less than 50° F or greater than 95° F or as
set by the user.

High Ripple Current

Charger

Greater than 5 amps RMS per ampere-
hour or as set by the user.