User’s guide, Battery management system – APC Battery Management System User Manual

Page 57

Advertising
background image

®

USER’S GUIDE

Battery Management System

50

Syslog Server Settings

Server IP/
Domain
Name

Uses specific IP addresses or domain names to identify which of up to four
servers will receive Syslog messages sent by the Battery Management
System.

N

OTE

:

To use the Syslog feature,

Server IP/Domain Name

must be

defined for at least one server.

Port

Identifies the user datagram protocol (UDP) port that the Battery
Management System will use to send Syslog messages. The default is

514

, the number of the UDP port assigned to Syslog.

Local Priority (Severity Mapping)

Map to
Syslog’s
Priorities

Maps each of the severity levels (

Local Priority

settings) that can be

assigned to Battery Management System and embedded management
card events to the available Syslog priorities. The following definitions are
from RFC3164:

Emergency

: The system is unusable

Alert

: Action must be taken immediately

Critical

: Critical conditions

Error

: Error conditions

Warning

: Warning conditions

Notice

: Normal but significant conditions

Informational

: Informational messages

Debug

: Debug-level messages

Following are the default settings for the four

Local Priority

settings:

Severe

is mapped to

Critical

Warning

is mapped to

Warning

Informational

is mapped to

Info

None

(for events that have no severity level assigned) is mapped to

Info

N

OTE

:

To disable sending Syslog messages for

Severe

,

Warning

, or

Informational

events, see

Actions Option (Web interface only)

.

Setting

Definition