System management cards, Use xmodem to upgrade one battery management, System management card – APC Battery Management System User Manual

Page 173: User’s guide, Battery management system

Advertising
background image

®

USER’S GUIDE

Battery Management System

166

Use FTP or SCP to upgrade multiple Battery
Management System Management Cards

To upgrade multiple Battery Management System Management Cards
using an FTP client or using SCP, write a script which automatically
performs the procedure. For FTP, use the steps in

Use FTP or SCP to

upgrade one Battery Management System Management Card

.

Use XMODEM to upgrade one Battery Management
System Management Card

To use XMODEM to upgrade the firmware for a single Battery Management
System Management Card that is not on the network:

1. Select a serial port at the local computer and disable any service which

uses that port.

2. Connect the serial cable that came with the Battery Management

System to the selected port and to the serial port at the Management
Card.

Modbus and the control console share a common serial port.
You can use either one or the other to access the Battery
Management System.

See also

If you are using Modbus to access the Battery Management
System, you must configure the DIP Switches. For DIP switch
configuration, see “Configure the DIP Switches” in the
Installation and Quick Start Manual (

.\doc\en\insguide.pdf

),

provided in Portable Document Format (PDF) on the APC
Battery Management System Utility CD and in printed form.