Installation – Lincoln Electric IM510 RANGER 8 User Manual

Page 14

Advertising
background image

A-7

INSTALLATION

RANGER 8

A-7

115 V Duplex Receptacles

The 115V auxiliary power receptacles should only be
used with three wire grounded type plugs or approved
double insulated tools with two wire plugs.

The current rating of any plug used with the system
must be at least equal to the current load through the
associated receptacle (Refer to Tables I and II). Do
not attempt to connect power receptacles in parallel.

Motor Starting

Most 1.5 hp AC single phase motors can be started if
there is no load on the motor or other load connected
to the machine, since the full load current rating of a
1.5 hp motor is approximately 20 amperes (10
amperes for 230 volt motors). The motor may be run
at full load when plugged into only one side of the
duplex receptacle. Larger motors through 2 hp can be
run provided the receptacle rating as previously stated
is not exceeded. This may necessitate 230V opera-
tion only.

GND

115 V

115 V*

230 V

*Current Sensing for Automatic Idle.
(Receptacle viewed from front of Machine)

Load From

K1418-1 and K1419-1 K1418-2, K1419-2 and K2160-1

115V/230V

CSA Machines

Dual Voltage

Each Half of

Total From

Each Half of

Total From

Receptacle

Each 115V

Both 115V

Each 115V

Both 115V

Duplex

Duplexes

Duplex

Duplexes

0

20*

70

15

60

1.1 KW

20*

60

15

60

3.4 KW

20*

40

15

40

5.7 KW

20*

20

15

20

8.0 KW

0

0

0

0

TABLE I Maximum Current Draw from 115V Duplex Receptacles - No Welding

*NEMA 5-20P Plug required for 20Amp Draw

Load From

K1418-1 and K1419-1 K1418-2, K1419-2 and K2160-1

115V/230V

CSA Machines

Dual Voltage

Each Half of

Total From

Each Half of

Total From

Receptacle

Each 115V

Both 115V

Each 115V

Both 115V

Duplex

Duplexes

Duplex

Duplexes

0

15

40*

15

30**

1.1 KW

15

40*

15

30**

3.4 KW

15

40*

15

30**

5.7 KW

15

20*

15

20**

8.0 KW

0

0

0

0

TABLE II Maximum Current Draw from 115V GFCI Duplex Receptacles - No Welding

*Maximum current draw from each 115V GFCI Duplex is 20 amps
*Maximum current draw from each 115V GFCI Duplex is 15 amps

Advertising