INSTALLATION

RANGER 8

A-9

Standby Power Connections

The Ranger 8 is suitable for temporary, standby, or
emergency power using the engine manufacturer’s
recommended maintenance schedule.

The Ranger 8 can be permanently installed as a
standby power unit for 230V-3 wire, single phase 35
ampere service.
(Connections must be made by a licensed electri-
cian who can determine how the 115/230V power
can be adapted to the particular installation and
comply with all applicable electrical codes.) The

following information can be used as a guide by
the electrician for most applications (refer also to
the connection diagram shown in Figure 1.)

1. Install a double pole, double throw switch between

the power company meter and the premises
disconnect.

Switch rating must be the same or greater than
the customer’s premises disconnect and service
overcurrent protection.

2. Take necessary steps to assure load is limited to

the capacity of the Ranger 8 by installing a 35 amp
230V double pole circuit breaker. Maximum
rated load for the 230V auxiliary is 35 amperes.
Loading above 35 amperes will reduce output
voltage below the allowable -10% of rated
voltage which may damage appliances or other
motor-driven equipment.

3. Install a 50 amp 115/230V plug (NEMA type 14-50)

to the Double Pole Circuit Breaker using No. 8,
4 conductor cable of the desired length. (The
50 amp 115/230V plug is available in the
optional plug kit.)

4. Plug this cable into the 50 amp 115/230V

receptacle on the Ranger 8 case front.

WARNING

Auxilliary Power While Welding

It must be noted that the above auxiliary power ratings
are with no welding load. Simultaneous welding and
power loads are permitted by following Table III. The
permissible currents shown assume that current is
being drawn from either the 115V or 230V supply (not
both at the same time). Also, the “Output Control” is
set at “10” for maximum auxiliary power.

TABLE III

SIMULTANEOUS WELDING AND POWER

Output Selector

Permissible Power

Permissible Auxiliary

Setting

Watts (Unity Power

Current in Amperes

Factor)

@ 115V -or- @ 230V

Max. Stick or Wire

Feed Setting

None

0

0

175 Stick Setting

2100

18

9

125 Stick Setting

3800

32

16

90 Stick Setting

5000

42

21

70 Stick Setting

5600

48

24

50 Stick Setting

6300

54

27

NO WELDING

8000

70