Auxiliary power, 115v duplex receptacles – Lincoln Electric IM511 RANGER 9 User Manual

Page 21

Advertising
background image

-19 -

Auxiliary Power

The Ranger 9 can provide up to 9,000 watts of
115/230 volts AC, single phase 60HZ power for contin-
uous use. The front of the machine includes three
receptacles for connecting AC power plugs. The
K1420-1 has one 50 amp 115/230 volt NEMA 14-
50R receptacle and two 20 amp 115 volt NEMA 5-
20R receptacles. The K1420-2 CSA machine has one
50 amp 115/230 volt NEMA 14-50R receptacle and
two 15 amp 115 volt NEMA 5-15R receptacles. Do
not connect any plugs that connect to the power
receptacles in parallel.

Start the engine and set the “IDLER” control switch to
the desired operating mode. Set the “CONTROL” to
10. Voltage is now correct at the receptalces for
auxiliary power.

115/230 Volt Dual Voltage Receptacle

The 115/230 volt receptacle can supply up to 40 amps
of 230 volt power to a two wire circuit, up to 40 amps
of 115 volt power from each side of a three wire circuit
(up to 80 amps total). Do not connect the 115 volt
circuits in parallel. Current sensing for the automatic
idle feature is only in the leg of the three wire circuit as
shown below.

Maximum Current Draw from 115V Duplex
Receptacles - No Welding

Maximum Current Draw from Optional 115V
GFCI Duplex Receptacles - No Welding

EACH

HALF OF

EACH 115V

DUPLEX

TOTAL

FROM

BOTH 115V
DUPLEXES

EACH

HALF OF

EACH 115V

DUPLEX

TOTAL

FROM

BOTH 115V
DUPLEXES

K1420-1

K1420-2 (CSA)

and K1421-1 (CSA)

LOAD FROM

115V / 230V

DUAL VOLTAGE

RECEPTACLE

0

2.2 KW

4.5 KW

6.7 KW

9.0 KW

20 *

20 *

20 *

20 *

0

78

60

40

20

0

15

15

15

15

0

60

60

40

20

0

EACH

HALF OF

EACH 115V

DUPLEX

TOTAL

FROM

BOTH 115V
DUPLEXES

EACH

HALF OF

EACH 115V

DUPLEX

TOTAL

FROM

BOTH 115V
DUPLEXES

K1420-1*

(WITH GFCI’S)

K1420-2

**

and

K1421-1

**

(WITH GFCI’S)

LOAD FROM

115V / 230V

DUAL VOLTAGE

RECEPTACLE

0

2.2 KW

4.5 KW

6.7 KW

9.0 KW

15

15

15

15

0

40

40

40

20

0

15

15

15

15

0

30

30

30

20

0

* Maximum current draw from each 115V GFCI Duplex is 20 amps.
** Maximum current draw from each 115V GFCI Duplex is 15 amps.

* NEMA 5-20P plug required for 20 amp draw.

115V Duplex Receptacles

The 115V auxiliary power receptacles should only be
used with three wire grounding type plugs or approved
double insulated tools with two wire plugs.

GND

115 V

115 V

230 V

* Current Sensing for Automatic Idle
(Receptacle viewed from front of machine.)

*

Advertising