Analog output 4-20 ma, Relay contact ratings, Dimensions – AW Gear Meters FEM-03 User Manual

Page 10: Input and output wiring connections, Fem-03 flow monitor

Advertising
background image

FEM-03 Flow Monitor

Operation and Programming Manual

9


Analog Output 4-20 mA

self-powered loop output into a maximum 400 Ohm load impedance

Relay Contact Ratings

Maximum
Switched
Power

Resistive Load

DC: 60W
AC: 125VA

Inductive Load

DC: 30W
AC: 60VA

Maximum Switched Voltage

220V DC, 250V AC

Maximum Switched Current

2A

Rated
Load

Resistive Load

DC: 30V, 2A
AC: 110V, 0.5A

Inductive Load

DC: 30V, 1A
AC: 110V, 0.3A

Do not use 115 VAC through relay contacts. Use 24 VDC instead.

Dimensions

Input and Output Wiring Connections

Make all connections to the FEM-03 from the back of the unit. A plug-in connector from the wall plug-
type power supply, normally supplied with the unit, delivers power. If necessary, any standard AC wall
plug unit providing 13-17VAC/250mA. or 18-24VDC/250mA. may be used. A standard female plug
(2.1mm I.D. x 5.5mm O.D.) supplies AC or DC power to the FEM-03. This connector is polarity insensitive.
The factory recommends tying one of the DC COMMON terminals to earth ground, especially for DC
operation.

Make all other connections through the two rear terminal connectors. Called the “upper” and “lower”
connectors, they are removable and have ten connections each. A label on each connector shows
connection information. Refer to the Connection Diagram on page 12 for details and typical

Caution

Advertising