Serial error codes, Checksum calculation, Fem-03 flow monitor – AW Gear Meters FEM-03 User Manual

Page 37

Advertising
background image

FEM-03 Flow Monitor

Operation and Programming Manual

36


Serial Error Codes

If a read or write operation is not successful, the Fem-03 returns one of the following error messages:

NO1cr – Undefined command (something other than K/J)

NO2cr – allowable read range exceeded (addresses 0 to 500 [000H to 01F4H] allowed)

NO3cr – read error (read request exceeded 12 characters)

NO4cr – FEM detected a checksum error in the lower byte

NO5cr – FEM detected a checksum error in the higher byte

Checksum Calculation

The checksum calculation for the string variables in the Rate A PL read command would be as follows:

>01K000004XXcr

^^^^^^^^^^.......these characters are used in the calculation.

Add the values for the ASCII Decimal variables.

HEX 0 + 1 + K + 0 + 0 + 0 + 0 + 0 + 4
ASCII 48 + 49 + 75 + 48 + 48 + 48 + 48 + 48 + 52 = 464

To calculate the final checksum, convert the decimal number 464 into HEX (464=1D0 hex) and take the
last two characters (D0). The final string would look like this:

>01K000004D0cr

ASCII characters needed for checksum calculations are:

ASCII

Decimal ASCII Decimal

0

48

A

65

1

49

B

66

2

50

C

67

3

51

D

68

4

52

E

69

5

53

F

70

6

54

7

55

8

56

J

74

9

57

K

75