FEM-03 Flow Monitor

Operation and Programming Manual

32


TIME PRINT

The FEM-03 prints the following:

the current elapsed time since power-on

a sequential printout number

Rate A

PL

Rate B

PL

Job TOTAL A

Job TOTAL B

These print at a specified time interval in Hours. Valid numbers are 00.001 Hours (3.6 seconds) to 10.000
Hours. TIME PRINT reverts to a disabled state whenever power to the FEM is removed, and must be
reactivated after each power cycle.

DO NOTHING (hardware print request)

In this mode, the FEM-03 will “do nothing” until the hardware input is recognized. The FEM-03 RS232
Receive input is used to request a printout. When this mode activates, each momentary connection of
the FEM-03 RS232 RX input (terminal DN 5) to 15VDC (terminal DN 1) causes the FEM-03 to print:

the current elapsed time since power-on

a sequential printout number

Rate A

PL

Rate B

PL

Job TOTAL A

Job TOTAL B

Once this or any PRINTER function is active, the hardware print request input is also active and remains
active (even when power is reapplied to the FEM-03) until the user deactivates the PRINTER from the
programming screen.

SYSTEM INFO PRINT

Initiates a printout of all the programmed values contained in the FEM-03, providing up to 46 pieces of
information, depending on model.

SINGLE PRINT

This mode initiates a single printout of:

the current elapsed time since power-on

a sequential printout number

Rate A

PL

Rate B

PL

Job TOTAL A