Fem-03 flow monitor – AW Gear Meters FEM-03 User Manual

Page 40

Advertising
background image

FEM-03 Flow Monitor

Operation and Programming Manual

39


Read/Write Variables

Address

Length

Data (Cont’d)

Serial Speed

00C2H

1Byte

1=9600 Baud

2=19200 Baud

3=38400 Baud

4=57600 Baud

Unit Number (communication offset)

00BFH

1Byte

Default is 01

FEM Serial Command Variables

Address

Length

Data

Serial RESET TOTAL Command

00C4H

1Byte

will return to 0

1=Resets Job A

2= Resets Job B

3= Resets Jobs A and B

4=Resets Grand and Job A

5-Resets Grand and Job B

6=Resets All


Update EEPROM Command

00C5H

1Byte

will return to 0

Any number except 0

moves all Run time Variables to
the EEPROM location.

RELAY Override Command

00C6H

1Byte

write zero to release

80H Relay 1 and Relay 2 ON

81H Relay 1 OFF and Relay 2 ON

82H Relay 2 OFF and Relay 1 ON

83H Relay 1 and 2 OFF

Force mA Output Command

002DH

2Bytes

MSB first

(FEM-03 and -03A2 only)
Writing any number between 1
and 4095 (0001Hex and 0FFF Hex)
activates the mA output where: 1
= .005mA and 4095 = 20mA.
Writing a 0 returns the control to
the FEM-03.

Example QBASIC Program for Protocol Communications

Below is a QBASIC program that allows the user to communicate with the FEM-03 by initiating serial
port #1 at 9600 baud and prompting the user for read or write strings. The program assembles strings
following the OPTO 22 protocol format described on page 34. All string data must be in Hex notation. Do
not enter the > sign before the string and do not calculate the checksum. The program calculates the
checksum, assembles the string, adds the cr, and sends the string to the FEM.