FEM-03 Flow Monitor

Operation and Programming Manual

18


LIMITS

The FEM-03 has two programmable limit outputs: L1 and L2. The LIMIT display shows:

to what function each limit is assigned

the value (in engineering units) at which each limit becomes active

the current status of the limit outputs

The limit values are displayed using KFR or KFT, decimal location, and engineering units corresponding to
the limit assignment. See LIMITS Programming on page 28 for information regarding limit programming
and operation.

ANALOG OUT (FEM-03A, -03A2 and -03Ax only)

ANALOG OUT displays the analog output value in milliAmps. The two-digit number shown after ANALOG
OUT indicates which signal the output represents. For a listing of available output assignments and
corresponding numbers, see ANALOG OUT Programming on page 27.

BATCH TOTAL

BATCH TOTAL displays the JOB A TOTAL, and the S1 and S2 TOTAL LIMIT activation levels. When the
FEM-03 is programmed for BATCH TOTAL operation, both are assigned as TOTAL A limits based on the
KFT, decimal point, and engineering units. The TOTAL limit activation levels will display unless assigned
to another function. If so assigned, the S1 or S2 display reads XXXX to indicate that it is not assigned to
JOB A TOTAL function. See BATCH TOTAL Programming on page 30 for information regarding
programming.

RATE A DR (FEM-03A2 and -03Ax only)

RATE A DR displays the flow rate with a + or – sign to indicate direction. This display mode displays RATE
A

PL

based on the programmed KFR A, decimal point, and engineering units. RATE A DR requires a B

channel signal that is 90° phase shifted from the A channel signal to correctly determine flow direction.