Fem-03 flow monitor – AW Gear Meters FEM-03 User Manual

Page 39

Advertising
background image

FEM-03 Flow Monitor

Operation and Programming Manual

38


Read/Write Variables

Address

Length

Data

Rate A (PL measurement)

0000H

4Bytes

MSB first

Rate A (GT measurement)

0037H

4Bytes

MSB first

Job Total A (READ ONLY)

0004H

4Bytes

MSB first

Grand Total A (READ ONLY)

0020H

4Bytes

MSB first

A-KFR for Rate

0071H

2Bytes

MSB first

A-KFR decimal point location

0075H

1Byte

A-KFT for Total

0073H

2Bytes

MSB first

A-KFT decimal point location

0076H

1Byte

A-Rate Engineering units

0085H

5Bytes

Array last digit 0

A-Total Engineering units

008FH

5Bytes

Array last digit 0

A-Flow Direction

00BEH

1Byte

Rate B (PL measurement)

000EH

4Bytes

MSB first

Rate B (GT measurement)

003BH

4Bytes

MSB first

Job Total B (READ ONLY)

0012H

4Bytes

MSB first

Grand Total B (READ ONLY)

0024H

4Bytes

MSB first

B-KFR for Rate

0077H

2Bytes

MSB first

B-KFR decimal point location

007BH

1Byte

B-Rate Engineering units

008AH

5Bytes

Array last digit 0

B-KFT for Total

0079H

2Bytes

MSB first

B-KFT decimal point location

007CH

1Byte

B-KFT for Total engineering units

0094H

5Bytes

Array last digit 0

Limit 1 Mode

00B3H

1Byte

1=Rate A Gate time

2=Rate A Pulse length

3=Rate B Gate time

4=Rate B Pulse length

5-Totalizer A

6=Totalizer B

Limit 1 (could be Rate or Total)

00B4H

4Bytes

MSB first

Margin 1 for rate limit

00DEH

4Bytes

MSB first

Limit 2 Mode

00B8H

1Byte

1=Rate A Gate time

2=Rate A Pulse length

3=Rate B Gate time

4=Rate B Pulse length

5-Totalizer A

6=Totalizer B

Limit 1 2 could be Rate or Total)

00B9H

4Bytes

MSB first

Margin 2 for rate limit

00E2H

4Bytes

MSB first

Milli-amps Offset

00AFH

4Bytes

MSB first

Milli-amps Out

002BH

4Bytes

MSB first

Analog Out Mode

002AH

1Byte