Jumper setup, Installation instructions, Wiring diagram – Edwards Signaling FireShield 10 Zone User Manual

Page 14

Advertising
background image

Installation

2.4

FireShield Technical Reference Manual

Jumper setup

Jumper

Name

Description

J2

Reserved
for future
use

N/A

J3

Zone 6 -
10
jumper

Sets the five LEDs to report alarms
in zones 6 - 10. [1]

J4

Zone 1- 5
jumper

Sets the five LEDs to report alarms
in zones 1 - 5. [1]

J5

Group
jumper

Allows two FSRZI-As to be
connected to the same panel and
set to the same zone output option.

Install the jumper on FSRZI-As in
only one of the two groups.

[1] Install only one zone jumper on J3 or J4.

Note: For jumper location, refer to the FSRZI-A wiring
diagram.

Installation instructions

A single FSRZI-A can be mounted in a standard, single gang
electrical box (ANSI/NEMA OS1-1996) using the single gang
cover plate that is included. Up to three FSRZI-As with or
without an FSRSI can be mounted in an approved multiple
gang electrical box (ANSI/NEMA OS1-1996) with
appropriate two, three, or four gang cover plates (model
numbers FSAT-2, FSAT-3, or FSAT-4).

Caution:

Make sure all power is disconnected from the panel

before installing. Observe static-sensitive handling practices.

To install the FSRZI-A:

1. Verify that all field wiring is free of opens, shorts, and

ground faults.

2. Connect wires to the FSRZI-A as shown (see wiring

diagram).

3. Using the two plain machine screws provided, mount the

module to the electrical box.

Note:

If you are surface mounting the FSRZI-A, you must

install washers (provided) between the FSRZI-A and the
surface mount box.

4. Using the two white machine screws provided with the

faceplate, mount the faceplate to the module.

5. Connect the wires to the terminals in the control panel.

6. Program the FSRZI-A using the Find Annunciators

program option. Refer to Chapter 3 “Programming.”

Compatible electrical box

Installing the FSRZI-A in an electrical box

Wiring diagram

J5

J4

J3

J2

24 V out +

24 V out -

24V IN

- +

C IN

+ -

C OUT

+ -

24V OUT

- +

24 V in +

24 V in -

Communication in -

Communication in +

Communication out +

Communication out -

From control
panel or
previous
device

To next device

Notes

1. All wiring is supervised and power limited.

2. 24 V out (aux power) must be programmed as non-

resettable.

Advertising
This manual is related to the following products: