Panel specifications, Appendix d – Edwards Signaling FireShield 10 Zone User Manual

Page 59

Advertising
background image

FireShield Technical Reference Manual

D.1

Appendix D

Panel specifications

FS302 three-zone
panel

FS502 five-zone panel

FS1004 ten-zone panel

Class B

3

5

3

1

10

8

6

4

2

0

Initiating device
circuits (IDCs)

Class A

0

0

1

2

0

1

2

3

4

5

Class B

2

2

0

4

2

0

Notification appliance
circuits (NACs)

Class A

0

0

1

0

1

2

Power supply

2.0 amps total

3.0 amps total

3.0 amps (expandable to 5.5 amps)

NAC voltage rating

24 Vfwr

Maximum NAC current

1.5 amps each

1.5 amps total

1.5 amps each

2.5 amps total

1.5 amps each - 2.5 amps total for

NAC1 + NAC2 or NAC3 + NAC4

5.0 amps with optional

expander transformer

120 Vac 60 Hz

0.8 amps

0.8 amps

1.6 amps - incl. optional exp. transformer

AC input

230 Vac 50/60 Hz

0.4 amps

0.4 amps

0.8 - incl. optional exp. transformer

Base panel current draw (standby)

110 mA

120 mA

145 mA

Base panel current draw (alarm)

145 mA

170 mA

250 mA

Battery placement

Up to two 7 Ah batteries will fit in the panel.
Note: If batteries greater than 7 Ah are required,
you must use the BC-2 battery cabinet. Refer to
installation sheet P/N 3100027.

Up to two 18 Ah batteries will fit in the
panel.

Maximum auxiliary current

0.5 amps (may be programmed as resetable)

Auxiliary output

19 to 25.7 Vdc

IDC max. detector standby current

1.5 mA (See FireShield UL and ULC Compatibility List (P/N 3100468)

for maximum quantity of detectors per circuit.)

IDC circuit

Maximum loop resistance: 13

Maximum loop capacitance: 0.03

µ

F

IDC operating voltage

16.3 to 25.7 Vdc

Compatibility ID

100

Alarm contact

Form A N.O. 30 Vdc @ 1 A (resistive load)

Trouble contact

Form C 30 Vdc @ 1 A (resistive load)

Supervisory contact

Form A N.O. 30 Vdc @ 1 A (resistive load)

Environmental

Temperature: 0 to 49 °C (32 to 120 °F)

Humidity: 5 to 93% RH, noncondensing

Terminal rating

All terminals rated for 12 to18 AWG (0.75 to 2.5 sq mm)

Serial communications

Asynchronous communications maximum resistance: 13

Maximum capacitance: 0.03

µ

F

Batteries

Batteries must be sealed lead acid type only. Maximum charging capacity = 18 Ah.

Advertising
This manual is related to the following products: