Edwards Signaling FireShield 10 Zone User Manual

Page 39

Advertising
background image

Programming

FireShield Technical Reference Manual

3.17

The system takes you back to the beginning of FSDACT
programming (Program DACT).

2. Remove the program jumper PRG.

You can store the jumper on one pin of the jumper.

Editing previously programmed information

You may find it necessary to change information that you
previously programmed (e.g. if a phone number changes).

To edit previously programmed information:

1. Install program jumper PRG.

2. Press Remote Disconnect until “DACT Programming” is

displayed.

3. Press Reset until Yes selected.

4. Press Panel Silence to save.

5. Enter

your

passcode.

6. Press Remote Disconnect to advance to the programming

option you want to change.

The currently stored data is displayed.

7. Edit the program option with the desired setting.

Use the program buttons to enter the information.

8. Press Panel Silence to save.

9. Edit other program options as needed.

10. Exit from program mode by removing jumper PRG.

Other FSDACT options

The following options can only be changed using the
FireShield Configuration Utility. Refer to the FireShield
Configuration Utility online help system for details on
programming these options.

Swinger shutdown

Description: Automatically inhibits transmission of a single
event more consecutive times than the value entered.

Format: 0 – 255

Default: 0 (none)

Contact ID

Contact ID codes can only be changed when using the
configuration utility.