Installation instructions, Wiring diagram, Service and troubleshooting – Edwards Signaling FireShield 10 Zone User Manual

Page 16

Advertising
background image

Installation

2.6

FireShield Technical Reference Manual

Installation instructions

The FSRRM snaps into a snap track (shipped with the
FSRRM), which mounts inside a listed fire alarm enclosure.
The FSRRM can be positioned in the snap track with the
terminal block facing vertically or horizontally.

Caution:

Make sure all power is disconnected from the panel

before installing. Observe static-sensitive handling practices.

To install the FSRRM:

1. Mount the MFC-A cabinet using the installation sheet

provided (P/N 387453).

2. Drill mounting holes in the snap track using the template

provided (P/N 3100463). These holes will align to the
mounting holes on the MFC-A. An optional extended
track (P/N FSRRM-S11) is available for mounting two to
four FSRRM modules.

3. Mount the snap track to the MFC-A cabinet.

MFC-A

Snap

track

Snap

track

MFC-A

Snap

track

Snap

track

4. Insert one side of the FSRRM into the first snap track slot

and snap in the opposite side.

RRM

Snap track

Mount in first

slot only

5. Verify that all wiring is free of opens, shorts, and ground

faults.

6. Connect the FSRRM to the panel or other peripheral

devices.

7. Power up the panel and confirm that all relays are in the

correct state before connecting the field wiring.

8. Connect field wires to the FSRRM as shown in the wiring

diagram. Be sure connection will not adversely affect
controlled devices (e.g. elevators, fans, etc.).

9. Connect wiring to the controlled devices.

10. Program the FSRRM using the Find Annunciators

program option. Refer to Chapter 3 “Programming.”

Wiring diagram

24V IN

+ -

C IN

- +

C OUT

- +

OUT 3

NO C NC

OUT 1

NO C NC

OUT 2

NO C NC

OUT 4

NO C NC

OUT 5

NO C NC

24V OUT

+ -

X

24 V in +

24 V in -

Communication in -

Communication in +

24 V out +

24 V out -

Communication out -

Communication out +

From control panel
or previous device

To next device

To next device

[1]

[1]

[1]

[2]

[2]

[2]

[2]

[2]

[1]

Notes

[1] Supervised and power limited.

[2] Must be connected to a power limited source.

3. 24 V out (aux power) must be programmed as non-

resettable.

Service and troubleshooting

If the Disabled and Annunc Trouble LED are lit but no IDC or
NAC is disabled then the FSRRM output is disabled.

Advertising
This manual is related to the following products: