Frame these instructions and mount on the wall next to the control panel.

Operating Instruction Placard

P/N: 3100470 REV: 2.0

FireShield - Fire Alarm Control Panel

1 / 1

FireShield Fire Alarm Control Panel

Operating Instructions

For additional information, refer to the FireShield
Technical Reference Manual
P/N 3100353.

RESPONDING TO ALARM SIGNALS
1. Evacuate the area.
2. Notify the proper authorities immediately and state

the nature and location of the emergency.

3. Be prepared to provide directions to firefighters when

they arrive.

TO SILENCE ALARM NOTIFICATION SIGNALS

WARNING! Alarm notification signals should not be
silenced until after all occupants have been evacuated.
1. Press Signal Silence & Drill.
The Signal Silenced LED turns on and all audible
notification circuits turn off. New alarm events turn the
notification circuits back on.
Note: Panel programming may delay alarm silence for up
to one minute, may prevent alarm silencing when water
flows through the sprinkler system, and may not turn off
visible notification circuits.

TO RETURN THE SYSTEM TO NORMAL AFTER AN
ALARM OR SUPERVISORY EVENT
1. Make sure all smoke detectors are free from smoke

and all manual pull stations are reset.

2. Press Reset.
Note: Panel programming may delay panel reset for up to
one minute after alarm notification circuits turn on.

TO INITIATE A FIRE DRILL
1. Press Signal Silence & Drill.
All audible notification circuits turn on. This function will
not automatically notify the fire department.

TO PERFORM A LAMP TEST (panel and remote
annunciators)

1.

Press and hold the Remote Disconnect and Walk
Test buttons simultaneously.

TO PERFORM A REMOTE ANNUNCIATOR LAMP
TEST

1.

Press and hold the Silence button on the RSI for
five seconds.

2.

LEDs on remote annunciators will remain on until
silence button is released.

RESPONDING TO TROUBLE SIGNALS
1. Silence the panel buzzer.
2. Investigate the cause of the trouble and notify the

authorized service personnel immediately.

TO SILENCE THE PANEL BUZZER
1. Press Panel Silence.
The buzzer turns off. Any new events turn the buzzer
back on. Trouble conditions not cleared resound the
buzzer after a predetermined time.

WARNING! Trouble conditions may affect the panel's
ability to provide early detection and indication of a fire.
Clear trouble conditions immediately.

RESPONDING TO SUPERVISORY SIGNALS
1. Silence the panel buzzer.
2. Investigate the cause of the supervisory signal and

notify the authorized service personnel immediately.

RESPONDING TO MONITOR SIGNALS
1. Silence the panel buzzer.
2. Investigate the cause of the monitor signal and notify

the authorized service personnel immediately.

PERIODIC TEST RECOMMENDATIONS

See “Maintenance,” in the FireShield Technical
Reference Manual
for test instructions and references.

Installed by

Name:

Company:

Address:

Phone:

Per NFPA 72

†

Protected Premises Fire Alarm System, Local

†

Auxiliary Fire Alarm System

†

Remote Supervising Station Fire Alarm System

†

Central Station

Date:

For service contact

Company:

Address:

Phone:

Acceptance Inspection by

Date: