Calculations

A.4

FireShield Technical Reference Manual

Notification appliance circuit maximum
wire length calculation

Use this worksheet to determine the maximum wire length of
a notification appliance circuit. Fill in one worksheet for each
NAC connected to the panel.

Wire length matrix

Wire lengths in the following table are based on a voltage drop
of 1.9 volts or 10% and total load at the end of the line.

Maximum wire length

Current
required

18 AWG

16 AWG

14 AWG

12 AWG

0.25

584

950

1460

2170

0.50

292

474

730

1084

0.75

194

316

486

722

1.00

146

236

364

542

1.25

116

190

292

434

1.50

92

158

242

362

Maximum signal loss allowed [1]

V

×

1000

Wire resistance per 1000 ft/pair [2]

÷

Total operating current required [3]

÷

A

Maximum circuit length

ft

Notes

[1] 1.6 V for 230 V at 50 Hz

1.8 V for 230 V at 60 Hz
1.9 V for 120 V at 60 Hz

[2] Use 3.5

for 12 AWG and 2.5 sq mm wire, 5.2

for 14

AWG and 1.5 sq mm wire, 8.0

for 16 AWG and 1.0 sq

mm wire, and 13.0

for 18 AWG and 0.75 sq mm wire.

[3] Use the filtered 20 Vdc Average Operating Current ratings

found on the installation or catalog sheet of each device.