background image

System overview and operation

FireShield Technical Reference Manual

1.3

Component descriptions

1

2

3

4

5

7

8

13

12

11

9

10

PRG

6

(1) Main AC wiring block and fuse holder:

Provides

connections for 120 or 230 volt AC (primary power) from
dedicated service. Includes a primary power fuse (5 A).

(2) Dual Transformer AC wiring block:

Ten-zone panel only.

Provides connections between primary side of both main and
expander transformer and 120 or 230 volt AC (fused primary
power).

(3) Transformer:

Changes 120 or 230 volt AC supply voltage

to 24 volt AC.

(4) Power expander transformer (XTR3A120, XTR3A230):

Optional. Available for the ten-zone panel only. Provides
additional primary power to increase the available NAC
current for the ten-zone panel.

(5) Main circuit board:

Provides connections for all circuits.

Also includes the operator interface.

(6) FSDACT plug:

Used to connect the FSDACT to the circuit

board.

(7) Operator Interface:

Includes operator controls, LED

indicators, and circuit identification labels.

(8) Cabinet enclosure:

Houses the panel electronics and

standby batteries. In some cases the batteries may be housed in
an external battery cabinet (BC-2).

(9) FSDACT:

Optional. Digital alarm communicator

transmitter. Provides LCD display for status messages and
programming menus. Provides two telephone line connections
for sending system messages to a compatible digital alarm
communicator receiver (DACR). Includes an event history log
of panel and FSDACT events.

(10) Program jumper PRG:

Used to place the panel in

programming mode.

(11) Tie wrap mounts:

Nonpower-limited. Used to secure

wires and to help maintain proper separation between power-
limited and nonpower-limited conductors.

(12) Tie wrap mounts:

Power-limited. Used to secure wires

and to help maintain proper separation between power-limited
and nonpower-limited conductors.

(13) Standby batteries:

Provide secondary/standby power to

the panel electronics in the absence of primary power.