List – SilentKnight VisorAlarm ARLY Interface User Manual

Page 30

Advertising
background image

VISOR ALARM – ARLY Configuration

II - 25

Doc.DM359-I

Rev.2.0

b) IO-CONF OUTPUT
Configures the general purpose output for signaling a specific condition in the VisorAlarm-
mIP/IPDACT system. Options given to the user are:

Automation-software-down. Communication between the VisorAlarm and Automation

Software is not active.

Alarm-pending. There is(are) signal(s), of any type, pending to be acknowledged by the

operator at the VisorAlarm receiver.

System-trouble-pending. There is(are) system trouble signal(s) pending to be acknowledged by

the operator at the VisorAlarm receiver.

Alarm-unrestored. There is(are) signal(s), of any type, pending to be restored to normal

conditions in the alarm system.

System-trouble -unrestored. There is(are) system trouble signal(s) pending to be restored to

normal conditions in the alarm system.

Syntax:

ARLY-1 Cfg>io-conf output <condition>
automation-software-down
alarm-pending
system-trouble-pending
alarm-unrestored
system-trouble-unrestored

condition

Condition to be signaled by the general purpose output:

Automation-software-down.
Alarm-pending.
System-trouble-pending.
Alarm-unrestored
System-trouble-unrestored.


Example:

ARLY-1 Cfg>io-conf output alarm-pending
ARLY-1 Cfg>


The default configuration sets the general purpose output to indicate System-trouble-unrestored at
VisorAlarm receiver.

2.7. LIST

Permits the user to list the configured parameters.
Syntax: