VISOR ALARM – ARLY Configuration

II - 45

Doc.DM359-I

Rev.2.0

Syntax:

ARLY-1 Cfg> MIP accnt subscriber-telephone telephone_number

telephone_number

This is the number that UD software dials to make an bi-directional
management operation with a Alarm Panel.


Example:

ARLY-1 Cfg> MIP 101234 SUBSCRIBER-TELEPHONE 914567898
ARLY-1 Cfg>

x) MIP accnt LAST-UPDATE-TIME
This parameter is for system use and it holds the date and time of the last configuration update for this
mIP/IPDACT device.
mip 90001234 anti-substitution enable
Syntax:

ARLY-1 Cfg> MIP accnt last-update-time "MM/DD/YY hh :mm :ss"

MM/DD/YY hh :mm :ss

Month/Day/Year Hour:Minutes:Seconds


Example:

ARLY-1 Cfg> MIP 101234 LAST-UPDATE-TIME "04/16/07 11:51:47"
ARLY-1 Cfg>

y) MIP accnt ANTI-SUBSTITUTION
This parameter is for system use and it defines if anti-substitution detection must be performed on this
device. With anti-substitution if a device is replaced with another device with a different serial number
a “System Trouble” signal will be raised and operation of the new device will be disabled.
Syntax:

ARLY-1 Cfg> MIP accnt anti-substitution flag

flag

enabled: Antisubstitution detection is performed on this device
disabled: Antisubstitution detection is no performed on this device


Example:

ARLY-1 Cfg> MIP 101234 ANTI-SUBSTITUTION enabled
ARLY-1 Cfg>

2.10. MONITOR-IP-ADDR

If the access network connection drops, it will stop receiving traffic from the registered
mIP/IPDACTs. Once the supervision timer times out, an alarm is generated for each registered
mIP/IPDACT. This situation can flood both the Automation Sw as well as the VisorALARM. To
avoid this, you can monitor the access to a configurable network address. If, after three attempts,