SilentKnight VisorAlarm ARLY Interface User Manual

Page 58

Advertising
background image

VISOR ALARM – ARLY Configuration

II - 53

Doc.DM359-I

Rev.2.0

ARLY-1 Cfg>UPDATE MIP 101234 RECEIVER-IP 172.24.78.99
ARLY-1 Cfg>

c) UPDATE MIP accnt RECEIVER-UDP-PORT
Configures the UDP port for connection with the distinct mIP/IPDACTs.
Syntax:

ARLY-1 Cfg>UPDATE MIP accnt RECEIVER-UDP-PORT port_number

port_number

Number of the UDP port used. Admits values between 1 and 65535.


Example:

ARLY-1 Cfg>UPDATE MIP 101234 RECEIVER-UDP-PORT 20300
ARLY-1 Cfg>

d) UPDATE MIP accnt USR-PASSWORD
Configures the mIP/IPDACT configuration / monitoring console password. This is applied to both the
asynchronous console as well as the telephonic console.
Syntax:

ARLY-1 Cfg>UPDATE MIP accnt USR-PASSWORD password

password

Password of up to 16 hexadecimal digits (0 to 9, A, B, C, D, E and F).


Example:

ARLY-1 Cfg>UPDATE MIP 101234 USR-PASSWORD 12FED00B3
ARLY-1 Cfg>

e) UPDATE MIP accnt MIP-PASSWORD
Configures the password with which the mIP/IPDACT encrypts its messages.
Syntax:

ARLY-1 Cfg>UPDATE MIP accnt MIP-PASSWORD password

password

Password of up to 16 hexadecimal digits (0 to 9, A, B, C, D, E and F).


Example:

ARLY-1 Cfg>UPDATE MIP 101234 MIP-PASSWORD 12FED00B3
ARLY-1 Cfg>

f) UPDATE MIP accnt RECEIVER-PASSWORD
Configures the password with which the VisorALARM encrypts its messages.
Syntax:

ARLY-1 Cfg>UPDATE MIP accnt RECEIVER-PASSWORD password

password

Password of up to 16 hexadecimal digits (0 to 9, A, B, C, D, E and F).

Advertising