VISOR ALARM – SEPI Configuration
III - 73
Doc.DM359-I
Rev.2.0
2.4. LIST
Lists the interface parameters with their corresponding values.
Syntax:
SEPI-serial0/1 Cfg>list all
Serial parameters
-----------------
Link speed.: 9600 (bit/sec)
Data bits..: 8
Stop bits..: 1
Parity.....: NONE
Interface parameters
--------------------
Flow control type.....: None
Interface buffer size.: 2048 (bytes)
2.5. NO
This command is used to negate another command or to reset the default configuration for a
determined parameter.
Syntax:
SEPI-serial0/1 Cfg>no parameter
description Remove interface description
serial-parameters Set default serial parameters
shutdown Change state to administratively up
In the section for each of the commands that can be preceded by the word “NO”, the effects of this
have been explained. For further information, please see the section on the required command.
2.6. SERIAL-PARAMETERS
Permits you to configure the serial port parameters. The configurable parameters are as follows:
SEPI-serial0/1 Cfg>serial-parameters ?
data-bits Set number of bits per character
parity Set character parity
speed Set speed
stop-bits Set number of stop bits per character
a) SERIAL-PARAMETERS DATA-BITS
Establishes the number of data bits. The available values are: 5, 6, 7 and 8. The default value is 8.
Syntax:
SEPI-serial0/1>SERIAL-PARAMETERS DATA-BITS number_data_bits
Example:
SEPI-serial0/1>SERIAL-PARAMETERS DATA-BITS 7
SEPI-serial0/1>