HT instruments HT7052 User Manual

Page 24

Advertising
background image

HT7052

EN - 22

6.6 DIAGNOSTIC

TEST

6.6.1 Setting of parameters
1. Switch on the instrument by pressing the ON/OFF key
2. Select with arrow keys  or  the item “DIAGNOSTIC TEST” on main menu and

confirm with SELECT key. The screen of Fig. 25 is shown by the meter. In case of
activation of Graphic R(t) option press arrow keys  or  to select the graphical
screen of Fig. 26

Fig. 25: Initial numerical screen

Fig. 26: Initial graphical screen


3. Press again the SELECT key to enter in the setup parameters section. The screen of

Fig. 27 is shown by the meter

4. Use the arrow keys  or  for the selection of parameters. The herewith Table 3

shows the meaning of the measurement parameters

5. Set the values by using the arrow keys  or . Press SELECT key to select possible

sub-parameters and repeat the settings

6. To activate the graphical screen the parameter Graph R(t) should be ON and the Timer

must be activated (see Fig. 27). The time duration of graphical function is
correspondent to the value of set Time3

7. The Timer value could be very long (up to 30 minutes), so the special automatic

decimation algorithm (LOG) is use to write the Graph R(t) at display (see Fig. 28)

8. The cursors of the Graph R(t) could be activated with  key at the end of

measurement. The cursors of the Graph R(t) could be moved with  or  keys

9. Press ESC key to save the settings and back to the measurement screen or the

START/STOP key to exit from the settings menu and activate the test

Parameter Description

Unominal

Set test voltage – Range 500V

10kV step 25V

Time1

Time to take R1min result

Time2

Time to take R1min result and calculate DAR

Time3

Time to take R3min result and calculate PI

DD ON/OFF

ON: DD enabled, OFF: DD disabled

Graph R(t)

Enable/Disable Graph R(t)

R(t)

Set of minimum and maximum values of R(t) for graphical
screen

R(t) Type

Set of “LIN” (linear) o “LOG” algorithm of graphical screen

Table 5: Setting of internal parameters

CAUTION

Time1

 Time2  Time3 are timers with the same start point. The value of

each presents the duration from the start of the measurement. The maximum
time is 30 min