KYORITSU 6202 User Manual

Page 10

Advertising
background image

3.6 Explanation for indications
3.6-1 M-6200 Display (common with M-6202)

Note. 1) Over range display: "OL" symbol is displayed on the LCD over range

display.

2) LINE = PHASE

3.6-2 LED for threshold value indication and buzzer

When exceeding following limit values which are defined in DIN
VDE0702:1995, LED lights up and buzzer sounds.

3.7 Applicable standards

Instrument operation: DIN VDE 0701:2000 / DIN VDE 0702:1995
Safety: IEC/EN61010-1 CATIII 300V-instrument

IEC/EN61010-2-031 CATIII 300V(600V)-test lead

8

Measuring range

Condition

LED for threshold
value indication

Warning buzzer
(continuous sound)

RPE >0.3

Ω

RPE >1

Ω

RINS < 0.5M

Ω

RINS < 2.0M

Ω

IEA >7.0mA

IEA >15mA

IL >0.25mA

IL >0.5mA








---


---

---

---

Protective conductor
resistance

Insulation resistance

Equivalent leakage
current

Leakage current /
contact current
(substantiation of

absence of voltage)

Fig.6

The Polarity of protective

earth conductor resistance

Power supply voltage
(Line-Neutral)

Current consumption

NULL indication

Units

Advertising