RE-DM4 Specifications

Suggested Loads

RE-DM4 Specifications

Dimensions (HW)

5.75" x 10.0" (146.50 mm x 254.00 mm)

Line Input

• 120, 240 VAC, single phase, 2W+G, 50/60 Hz, 2400 W, one feed

• 120, 120/240, 240 VAC, single phase, 3W+G, 50/60 Hz, 4800 W, dual feed

Output

• 1200 W max. per channel @120, 240 VAC

• 2400 W max. total, all four channels on with single 2400 W feed

• 4800 W max. total, all four channels on with dual 2400 W feeds

• Line input #1 goes to dimmer 1 and 3; line input #2 goes to dimmer 2 and 4

• All electrical ratings are for continuous duty

Wire rating

Use only copper wires rated at 75°C (167°F) min.

Torque terminals

To 20 in-lbs (2.3 N/M)

Maximum wire size

10 AWG (4 mm²)

Wire stripping length

0.5" (13 mm)

AxLink Port

4-pin 3.5mm black captive wire connector. AxLink communication
signaling with 12VDC power in.

Aux Power

2-pin 3.5mm green captive wire connector. This is a 12VDC power input that supplies
additional power to the Radia PCB and connected Radia modules.

Dry Contacts

• Emergency fire alarm relay connection - Closed relay activates preset 126.

Other control is locked out until relay opens.
Supports daisy chaining of up to 20 dimmers for this connection, with a maximum
current requirement of 200mA when daisy-chained.

• Failsafe connection - Works with a toggle switch - opening the switch triggers preset

128, closing the switch triggers preset 127.
Supports daisy chaining of up to 20 dimmers for this connection with a maximum
current requirement of 200mA when daisy-chained.

BTU/hr

• 300 single feed (2400 W);

• 600 dual feed (4800 W)

Idle current draw

• 75 mA @ 120 VAC,

• 50 mA @ 240 VAC, 100 mA VDC

RDM control current

2 at 200 mA @ 12 VDC with no additional power supply

Certifications

• FCC

• CE

• IEC-60950 Safety

• UL North America

Operating Temp Range • 0° to 40°C (32° to 104°F)

Included Accessories

• 2 4-pin 3.5mm captive wire connector (41-5047)

• 4 #8-32x1/2” F-point mounting screws

Required Enclosures

• RDA-ENC2 (FG606-10)

• RDA-ENC4 (FG606-11)

• RDA-ENC6/6B (FG606-12/13/15)

• RDA-ENC12B (FG606-14/16)