Conduit – AMX Radia Eclipse 4-Channel Dimmer Module RE-DM4 User Manual

Page 20

Advertising
background image

Installation

12

RE-DM4 and RE-DM6 RADIA Eclipse Dimmer Modules

Conduit

Conduit runs depend on the enclosures you use and their AMX Lighting modules. All enclosures have conduit
knockouts on the top for high-voltage connections, and knockouts on the bottom for low-voltage connections.

All conduit knockouts allow for 1/2, 3/4, and 1-inch (12.7 mm, 19.0 mm, and 25.4 mm) conduits as shown in
FIG. 11.

You should also consider these recommendations prior to installing enclosures:



Install separate conduit for lighting loads. The recommended knockout for loads is located on the
top center of the enclosure.



Install separate conduit for the 120 VAC wiring to the line input terminal block. The recommended

knockouts for incoming power feeds are located on the top-left and top-right sides of the AMX
Lighting enclosure.



Install separate conduit for low-voltage signals for dry closures and AxLink connections. The
recommended knockout for these control connections is located on the bottom of the enclosure.



Additional knockouts are on the bottom-left and bottom-right sides of the enclosures for alternate
low-voltage connections.

FIG. 11

Knockout locations (RDA-ENC2 used as example)

TOP

BOTTOM

LEFT SIDE

FRONT

RIGHT SIDE

B

A

C

A

C

A

E

G

F

A

E

D

D

Knockout

Knockout

Knockout

Knockout

Knockout

Knockout

All knockouts
are for 1/2" (1.26 cm),
3/4" (1.90 cm), and
1" (2.54 cm)
conduit

A = 3.94" (100.0 mm)
B = 6.03" (153.1 mm)
C = 3.00" (76.2 mm)
D = 1.00" (25.4 mm)
E = 9.75" (24.76 cm)
F = 6.00" (15.24 cm)
G = 11.90" (30.22 cm)

Install the control modules according to local and National Electrical Code (NEC) regulations.