The variable to be monitored can be selected seperately for each alarm via
configuration
The following variables can be monitored:

w process value

w control deviation xw (process value - set-point)

w control deviation xw + suppression after start-up or set-point change

As there is automatically a control deviation after starting up and after
set-point changes, however, the alarm is suppressed, until the signal was
within the limits once.

w Set-point

w Correcting variable y (controller output signal)

g

If measured value monitoring + alarm status storage is chosen (

ConF / Lim /

Fnc.x = 2), the alarm relay remains switched on until the alarm is resetted in the
error list (

Lim 1..3 = 1) or via interface.

3.4 Maintenance manager / Error list

In case of one or several errors, the extended operating
level always starts with the error list. A current entry
into the error list (alarm or error) is displayed by the
Err LED in the display.
For displaying the error list, pressing 1x Ù is necessary.
(with configuration as a controller, press 2x Ù).

Err LED status

Signification

Proceed as follows

blinks

Alarm due to

existing error

- Determine the error type in the error list via the error number
- Remove the error

lit

Error removed,
Alarm not

acknowledged

- Acknowledge the alarm in the error list pressing key È or Ì
- The alarm entry was deleted.

off

No error, all alarm entries deleted

g

Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital
input di1/2/3 or the Ò-key.
Configuration, see page 31:

ConF / LOGI / Err.r

g

If an alarm is still valid that means the cause of the alarm is not removed so far
(Err-LED blinks), then other saved alarms can not be acknowledged and deleted.

Error status

Signification

2

Existing error

Change to error status 1 after error removal

1

Stored error

Change to error status 0 after acknowledgement in error list

0

No error/message not visible, except with acknowledgement

Operation

16

Maintenance manager / Error list