6.3 Input scaling

When using current or voltage signals as input variables for

InP.1 or InP.2,

scaling of input and display values at parameter setting level is required. Specifi-
cation of the input value for lower and higher scaling point is in the relevant elec-
trical unit (mA / V).

6.3.1 Input

Inp

g

Parameters

InL.1 , OuL.1, InH.1 and OuH.1 are only visible if

ConF / InP.1 / Corr = 3 is chosen.
The parameters

InL and InH determine the input range

Example mA:
InL= 4 and InH 0 20 means, the measurement is from 4 to 20 mA.

a

For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings for

InL.1 and OuL.1 and for InH.1 and

OuH.1 must have the same value.

Parameter setting level

36

Input scaling

Digital 280-1

mA/V

phys.

unit

mA / V

phys. unit

OuH.x

OuL.x

InH.x

InL.x