Out.1 und Out.2

name

value range

description

default

O.Act

circuit direction of output OUT1

0

0

direct / open circuit principle

1

inverse / closed circuit priciple

Y.1

controller output Y1

0

0

not active

1

active

Lim.1
Lim.2
Lim.3

message limit value 1/2/3

0

not active

1

active

Out.1/2/3

FAi.1

message INP error

0

0

not active

1

active

fOut

forcing OUT1 (2) (only visible with BlueControl!)

0

0

no forcing

1

forcing via interface

Out.3

name

value range description

default

O.tYP

signaltype OUT3

0

0

relay / logic

1

0 ... 20 mA continuous

2

4 ... 20 mA continuous

3

0...10V continuous

4

2...10V continuous

5

transmitter supply

O.Act

circuit direction of output OUT3 (only visible with O.TYP=0 )

1

0

direct / open circuit principle

1

inverse / closed circuit priciple

Y.1

controller output Y1 (only visible with O.TYP=0)

0

0

not active

1

active

Lim.1

message limit value 1 (only visible with O.TYP=0)

1

0

not active

1

active

Lim.2
Lim.3

message limit value 2/3 (only visible with O.TYP=0)

0

0

not active

1

active

FAi.1

message INP-error (only visible with O.TYP=0)

1

0

not active

1

active

Out.0

-19999...

99999

scaling of analog output for 0% (0/4mA e.g. 0/2V, only visible

with O.TYP=1..5)

0

Out.1

-19999...

99999

scaling of analog output for 100% (20mA bzw. 10V, only

visible with O.TYP=1..5)

100

Configuration level

26

Configuration

Digital 280-1