The control parameters can be determined from the values calculated for delay
time T

u

, maximum rate of increase v

max

, control range X

h

and characteristic K ac-

cording to the formulas given below. Increase Xp, if line-out to the set-point os-
cillates.

Controller

Digital 280-1

Manual tuning

21

Formulas

K = Vmax * Tu

controller behavior Pb1 [phy. units]

td1 [s]

ti1 [s]

With 2-point and
3-point controllers,
the cycle time must
be adjusted to
t1 / t2 £ 0,25 * Tu

PID

1,7 * K

2 * Tu

2 * Tu

PD

0,5 * K

Tu

OFF

PI

2,6 * K

OFF

6 * Tu

P

K

OFF

OFF

3-point-stepping

1,7 * K

Tu

2 * Tu

Parameter adjustment effects

Parameter

Control

Line-out of disturbances

Start-up behaviour

Pb1 higher increased damping

slower line-out

slower reduction of duty cycle

lower

reduced damping

faster line-out

faster reduction of duty cycle

td1 higher reduced damping

faster response to disturbances faster reduction of duty cycle

lower

increased damping

slower response to disturbances slower reduction of duty cycle

ti1 higher increased damping

slower line-out

slower reduction of duty cycle

lower

reduced damping

faster line-out

faster reduction of duty cycle