Di2/3, 2-wire transmitter supply 7, Out3 transmitter supply 7, Electrical connections – West Control Solutions D280-1 User Manual

Page 7: Connection of input di1, If u, 6 7 di2/3, u, Wire transmitter supply, 6 out3 transmitter supply

Advertising
background image

Connection of input di1

3

Digital input, configurable as switch or push-button

Connection of outputs OUT1/2

4

Relay outputs 250V/2A normally open with common contact connection

Connection of output OUT3

5

g

logic (0..20mA / 0..12V)

h

voltage (0/2...10V)

i

current (0/4...20mA)

i

transmitter power supply

Connection of inputs di2/3

6 (option)

Digital inputs (24VDC external), galvanically isolated, configurable as switch or
push-button

Connection of output U

T

7 (option)

Supply voltage connection for external energization

Connection of bus interface

8 (option)

RS422/485 interface with Modbus RTU protocol

a

If U

T

and the universal output OUT3 is used there may be no external galvanic

connection between measuring and output circuits!

Electrical connections

Digital 280-1

Terminal connection

7

Option

+24VDC

5mA

5mA

0V

1

2

3

K

+

-

+

-

+

-

17,5V
22mA

OUT3

J

J

x

1

7

5

8

6

9

10

11

12

13

14

15

4

3

5

1

7

5

8

6

9

10

11

12

13

14

15

4

3

(2)

17

16

6 7 di2/3, U

T

2-wire transmitter supply

1

2

3

K

+

-

+

-

13V

22mA

7

8

9

10

11

12

13

14

15

6 OUT3 transmitter supply

Advertising