4 digital 280-1 with measured value output 33, Measured value output 33, Out3 – West Control Solutions D280-1 User Manual
Page 33: Configuration level
Advertising
5.3.4 Digital 280-1 with measured value output
ConF / Out.3: O.tYP = 1
Out.3 0...20mA continuous
=
2
Out.3 4...20mA continuous
=
3
Out.3 0...10V continuous
=
4
Out.3 2...10V continuous
Out.0 = -1999...9999
scaling
Out.3
for 0/4mA or 0/2V
Out.1 = -1999...9999
scaling
Out.3
for 20mA or 10V
O.Src=3
signal source for
Out.3 is
the process value
Configuration level
Digital 280-1
Configuration examples
33
phys.
unit
mA / V
phys. unit
Out.1
Out.0
0/4mA
0/2V
20mA
10V
U
Logic
OUT3
7
8
9
Advertising