Examples for self-tuning attempts

(controller inverse, heating or heating/cooling)

Start: heating power switched on
Heating power Y is switched off (1).
When the change of process value X
was constant during one minute (2),
the power is switched on (3).
At the reversal point, the self-tuning
attempt is finished and the new para-
meter are used for controlling to
set-point W.
Start: heating power switched off
The controller waits 1,5 minutes (1).
Heating power Y is switched on (2).
At the reversal point, the self-tuning
attempt is finished and control to the
set-point is using the new parameters.

Self-tuning at the set-point a
The process is controlled to the
set-point. With the control deviation
constant during a defined time (1),
the controller outputs a reduced cor-
recting variable pulse (max. 20%)
(2). After determination of the con-
trol parameters using the process cha-
racteristic (3), control is started using
the new parameters (4).

Three-point controller a
The parameter for heating and cooling
are determined in two attempts. The hea-
ting power is switched on (1). Heating
parameters

Pb1, ti1, td1 and t1

are determined at the reversal point. The
process is controlled to the set-point (2).
With constant control deviation, the con-
troller provides a cooling correcting va-
riable pulse (3). After determining its
cooling parameters

Pb2, ti2, td2

and

t2 (4) from the process characteristics , control operation is started using the new

parameters (5).

a

During phase 3, heating and cooling are done simultaneously!

Operation

Self-tuning

22

Pro-8

t

2

100%

Y

0%

X

W

Start r

1

3

t reversal point

blinks

t

100%

Y

0%

X

W

start r

1

2

t reversal point

blinks

t

2

100%

Y

0%

X

W

1

3

blinks

4

r t

Start r

t

+100%

Y 0%

-100%

X

W

t reversal

point

Start r

1

2

3

4

5

r t

Advertising