8 special functions 57, 1 start-up circuit 57, Start-up circuit 57 – West Control Solutions Pro-8 User Manual

Page 57

Advertising
background image

8.2 Boost function

The boost function causes short-time increase of the set-point, e.g. for removing
"frozen" material rests from clogged die nozzles with hot-runner control.

If configured (

® ConF/ LOGI/ booS), the boost function can be started via di-

gital input di1/2/3, with the function key on the instrument front panel or via the
interface (OPTION).

The set-point increase around boost set-point

PArA /SEtP/SP.bo remains ef-

fective as long as digital signal (di1/2 3, function key, interface) remains set. The
maximum permissible cycle time (boost time-out) is determined by parameter
PArA /SEtP/t.bo.
Unless reset after elapse of boost time I

t.bo, the boost function is finished by

the controller.

g

The boost function also works with

w

start-up circuit:

PArA /SEtP/ SP.bo is added to W after elapse of start-up

holding time

PArA /SEtP/ t.St.

w

Gradient function: set-point W is increased by

PArA /SEtP/ SP.bo with

gradient

PArA /SEtP/ r.SP.

Special functions

Pro-8

57

Boost function

W

Set-point

Process value

t

W +

SP.bo

SP.bo

Advertising