OUTPUTS

RELAY OUTPUTS OUT1, OUT2

Contact type:

KS5_-1_

0-_00_ _-_ _ _

KS5_-1_

1-_00_ _-_ _ _

KS5_-1_

2-_00_ _-_ _ _

KS5_-1_3-_00_ _-_ _ _
2 NO contacts with common connection
KS5_-1_

4-_00_ _-_ _ _

KS5_-1_

5-_00_ _-_ _ _

2 potentialfree change-over contacts

Max. contact rating:

500 VA, 250 V, 2A at 48...62 Hz,
resistive load

Min. contact rating:

6V, 1 mA DC

Operating life (electr.): 800.000 duty cycles with max. rating

OUT3 USED AS RELAY OUTPUT

Contact type:

potential-free changeover contact

Max.contact rating:

500 VA, 250 V, 2A at 48...62 Hz,
resistive load

Min. contact rating:

5V, 10 mA AC/DC

Operating life (electr.):

600.000 duty cycles with max.
contact rating

Note:
If the relays OUT1...OUT3 operate external contac-
tors, these must be fitted with RC snubber circuits to
manufacturer specifications to prevent excessive
switch-off voltage peaks.

OUT3 AS UNIVERSAL OUTPUT

Galvanically isolated from the inputs.

Freely scalable resolution: 11bits

Current output

0/4...20 mA configurable.
Signal range:

0...approx.22mA

Max. load:

£ 500 W

Load effect:

no effect

Resolution:

£ 22 mA (0,1%)

Accuracy

£ 40 mA (0,2%)

Voltage output

0/2...10V configurable
Signal range:

0...11 V

Min. load:

³ 2 kW

Load effect:

no effect

Resolution:

£ 11 mV (0,1%)

Accuracy

£ 20 mV (0,2%)

OUT3 used as transmitter supply

Output power:

22 mA /

³13 V

OUT3 used as logic output

Load

£ 500 W

0/

£20 mA

Load > 500

W

0/> 13 V

OUTPUTS OUT5, OUT6 (OPTION)

Galvanically isolated opto-coupler outputs.
Grounded load: common positive voltage.
Output rating: 18...32 VDC;

£ 70 mA

Internal voltage drop:

£ 1V with I

max

. Protective cir-

cuit: built-in against short circuit, overload, reversed
polarity (free-wheel diode for relay loads).

POWER SUPPLY

Dependent of order:

AC SUPPLY

Voltage:

90...260 V AC

Frequency:

48...62 Hz

Power consumption

approx. 7,0 VA

UNIVERSAL SUPPLY 24 V UC

AC voltage:

20,4...26,4 V AC

Frequency:

48...62 Hz

DC voltage:

18...31 V DC class 2

Power consumption:

approx.. 7,0 VA

BEHAVIOUR WITH POWER FAILURE

Configuration, parameters and adjusted set-points, con-
trol mode: Non-volatile storage in EEPROM

BLUEPORT FRONT INTERFACE

Connection of PC via PC adapter (see "Accessory
equipment"). The BlueControl software is used to
configure, set parameters and operate the controller.

BUS INTERFACE (OPTION)

Galvanically isolated
Physical:

RS 422/485

Protocol:

Modbus RTU

Transmission speed:

2400, 4800, 9600, 19.200 bits/sec

Address range:

1...247

Number of controllers per bus: 32
Repeaters must be used to connect a higher number of controllers.

ENVIRONMENTAL CONDITIONS

Protection modes

Front panel:

IP 65 (NEMA 4X)

Housing:

IP 20

Terminals:

IP 00

Permissible temperatures

For specified accuracy:

0...60°C

Warm-up time:

³ 15 minutes

For operation:

-20...65°C

For storage:

-40...70°C

Humidity

max. 95% rel. humidity
75% yearly average, no condensation

Technical data

64