5 configuration examples 41, 1 on-off controller / signaller (inverse) 41, Signaller 41 – West Control Solutions Pro-8 User Manual

Page 41

Advertising
background image

4.5 Configuration examples

4.5.1

On-Off controller / Signaller (inverse)

ConF / Cntr: SP.Fn = 0

set-point /cascade controller

C.Fnc = 0

signaller with one output

C.Act = 0

inverse output action
(e.g. heating applications)

ConF /

Out.1: O.Act = 0

output action

Out.1 direct

Y.1

=

1

control output Y1 active

PArA / Cntr:HYS.L

= 0...9999

switching difference below

SP

PArA / Cntr:HYS.H

= 0...9999

switching difference above

SP

PArA / SEtP:SP.LO

= -1999...9999

lower set-point limit for Weff

SP.Hi

= -1999...9999

upper set-point limit for Weff

g

For direct signaller action, the controller action must be changed
(

ConF / Cntr / C.Act = 1 )

Configuration level

Pro-8

41

Configuration examples

InH.1

InL.1

SP.LO

SP

SP.Hi

100%

0%

Out.1Â

InP.1Ê

HYS.H

HYS.L

setpoint

relay
output

process value

Advertising