3.6 Manual tuning

The optimization aid should be used with units on which the control parameters
shall be set without self-tuning.

For this, the response of process variable x after a step change of correcting va-
riable y can be used. Frequently, plotting the complete response curve (0 to
100%) is not possible, because the process must be kept within defined limits.
Values T

g

and x

max

(step change from 0 to 100 %) or

Dt and Dx (partial step re-

sponse) can be used to determine the maximum rate of increase v

max

.

y

=

correcting variable

Y

h

=

control range

Tu

=

delay time (s)

Tg

=

recovery time (s)

X

max

=

maximum process value

V

max

=

Xmax

Tg

=

{

{

x

t

= max. rate of increase of process value

The control parameters can be determined from the values calculated for delay time T

u

,

maximum rate of increase v

max

, control range X

h

and characteristic K according to the

formulas given below. Increase Xp, if line-out to the set-point oscillates.