Calibration level

g

Measured value correction (

CAL)

is visible only if

ConF / InP.1 / Corr = 1 or 2 is selected.

w

To access the calibration level, press the key Ù for 3 seconds and then the
key Ì to select the

CAL-Menu item. Press Ù to confirm.

w

If the password function is activated, a prompt for the

PASS is displayed.

In the calibration menu (

CAL), the measured value can be adapted. Two me-

thods are available :

Offset correction (

ConF/ InP.1 / Corr =1 ):

InL.1: The input value of the scaling point is displayed.

The operator must wait, until the process is at rest.
Subsequently, the operator acknowledges the input value by pressing
key Ù.

OuL.1: The display value of the scaling point is displayed.

Before calibration,

OuL.1 is equal to InL.1. The operator can correct

the display value by pressing keys ÈÌ .
Subsequently, he confirms the display value by pressing key Ù.