Electrical inspection, Precision air conditioning easicool™ ezre – Airedale EasiCool 6kW 64kW User Manual

Page 17

Advertising
background image

17

EasiCool EZRE Operational Manual 7610207 V1.0.0_02_2013

M

ain

te

nanc

e

Precision Air Conditioning

EasiCool™ EZRE

Service Tools / Test Equipment

Voltmeter

Screwdrivers / Allen Keys

Ammeter

Safety Equipment

Safety Glasses / Goggles

Maintenance

Electrical Inspection

Procedures

Electrical Connections

Ensure all electrical connections are tight and correctly terminated.

Electrical Earthing

Check that the unit is correctly earthed.

Voltage

Measure the voltage at the following points and record on the maintenance sheet:

Voltage at busbar

Dedicated power supply

Voltage at permanent supply

Control voltage at transformer (min 22.5V, max 25V)

The voltage measurements should be carried out with the unit MCB’s turned off.

EC Fan Interrogation

The EC fans can be interrogated by connecting a hardware interface kit to the fan and PC. The kit comprises of a USB

to RS232 9-pin “D-type” adapter. This should be installed on the PC with the software supplied with the kit. The “COM”

port of the USB to RS232 adapter should be assigned to a free COM port between COM 1 and COM 4 via the system

device manager.

Connect the RS232 to RS485 interface converter to the USB port of your PC via the USB to RS232 serial interface lead

and connect the RS485 output to the fan.
Tx += RS A

Tx - = RS B

Electrical Inspection

Task

Frequency

3 Mths

12 Mths

60 Mths

Check main power supply voltages

Check electrical terminals are tight.

Check for signs of hot spots / discolouration on power cables.

Check amperages are as per design.