Alarm 14: Low Return Temperature

This alarm indicates that the return air temperature has exceeded the return air temperature low limit. To prevent

nuisance alarms on initial fan start-up, the alarm is delayed for 2 minutes. When the return air temperature is above the

low limit the alarm is auto reset within the controller.

Alarm 15: High Return Humidity

This alarm indicates that the return air humidity has exceeded the return air humidity high limit. To prevent nuisance

alarms on initial fan start-up, the alarm is delayed for 2 minutes. When the return air humidity is below the high limit the

alarm is auto reset within the controller.

Alarm 16: Low Return Humidity

This alarm indicates that the return air humidity has exceeded the return air humidity low limit. To prevent nuisance

alarms on initial fan start-up, the alarm is delayed for 2 minutes. When the return air humidity is above the low limit the

alarm is auto reset within the controller.

Alarm 17: Hours Limit Compressor 1

This alarm indicates that the running hours of compressor 1 have exceeded the hours run threshold. This alarm is for

maintenance use only and the compressor will continue to operate. Before attempting to reset this alarm, the running

hours of compressor need to adjusted below the hours run threshold. Then this manual reset alarm can be cleared by

referring to resetting the Alarm.

Alarm 18 Hours Limit Compressor 2

This alarm indicates that the running hours of compressor 2 have exceeded the hours run threshold. This alarm is for

maintenance use only and the compressor will continue to operate. Before attempting to reset this alarm, the running

hours of compressor need to adjusted below the hours run threshold. Then this manual reset alarm can be cleared by

referring to resetting the Alarm.

Alarm 19: Hours Limit Main Fan

This alarm indicates that the running hours of the main fan have exceeded the hours run threshold. This alarm is for

maintenance use only and the main fan will continue to operate. Before attempting to reset this alarm, the running hours

of main fan need to adjusted below the hours run threshold. Then this manual reset alarm can be cleared by referring to

resetting the Alarm.

Alarm 20: Hours Limit Humidifier

This alarm indicates that the running hours of the humidifier have exceeded the hours run threshold. This alarm is for

maintenance use only and the humidifier will continue to operate. Before attempting to reset this alarm, the running

hours of humidifier need to reset. Then this manual reset alarm can be cleared by referring to resetting the Alarm.

Alarm 21: Clock Faulty

This alarm indicates that the controller’s real time clock is not operating correctly. During this alarm any time zones set-

up would be ignored. When the clock is operating normally the alarm will auto reset and the controller will resume any

time zones previously set-up.

Alarm 22: LAN Disconnected

This alarm indicates that there is a network communications fault between one or more units. If the unit is configured

as standby, the unit will automatically start-up and continue to operate until the network communications fault has been

rectified. This alarm is auto reset.

Alarm 23: High Pressure

This alarm indicates that the condenser pressure has exceeded the condenser high limit and DX cooling has switched

off. This alarm is manual reset and can be cleared by referring to resetting the Alarm.

Alarm 24: Frost Protection

This alarm indicates that the controller has disabled DX cooling to prevent frost damaging the heating coil. This alarm is

auto reset.

Alarm 25: High Conductivity Alarm

This alarm indicates that the mains water supply conductivity has exceeded the high conductivity limit and the humidifier

has been disabled. This alarm is manual reset and can be cleared by referring to resetting the Alarm.