EasiCool EZRE Operational Manual 7610207 V1.0.0_02_2013

M

ain

te

nanc

e

EasiCool™ EZRE

Precision Air Conditioning

Maintenance

Refrigeration

Service Tools / Test Equipment

Refrigerant Manifold gauges

Spanners

Voltmeter

Safety Equipment

Safety Glasses / Goggles

Gloves

Overalls

Procedures

HP / LP Safety Pressure Switch Settings

Check operating of HP / LP cut-out,

Settings

LP cut-out – (Manual reset)
Has a 2 minute delay on start-up (similar to a Low ambient kit) plus 60 second run delay.
Low pressure cut-out 1.5 +/- 0.2 Barg
HP switch (manual reset): High pressure switch 40.25 bar +/- 1 Barg

Compressor Oil Level (Full load)

Check the compressor oil level at full load. (record oil level)

Refrigeration

Task

Frequency

3 Mths

12 Mths

60 Mths

Compare the following and compare results with commissioning records.
Suction, Liquid and Discharge pressures.

Refrigeration system temperatures, Suction, Liquid and

Discharge. Record superheat and sub cooling readings.

Check each circuit sight glass for dryness

and bubbles for indication of leaks.

Head pressure control is maintained.

Record details on F-Gas record.

Check compressor oil level.