Troubleshooting

General Faults

POSSIBLE CAUSE

REMEDY / ACTION

Compressor not operating.

No power to compressor.

Check isolator, fuses, MCBs,

contactor and control circuit wiring.

Seized compressor, possibly due

to lack of oil, broken valve.

Replace compressor - investigate oil

trapping and general installation.

Defective compressor motor.

Check winding resistances -

replace compressor. If burnt out

follow burn out procedure using

suction line burn-out drier.

Compressor phase loss.

Check 3 phase supply to compressor.

Klixon out and does not reset.

Sometimes it takes up to 4 hours to

reset. Replace compressor if necessary.

Low pressure switch operated (large or

complete loss of refrigerant charge).

Repair leak and recharge system - if

completely out evacuate before charging.

Condenser fan motor thermal

trip open circuit.

Investigate and correct.

Noisy compressor.

Lack of oil.

Repair leaks if any, add oil if required

but not too much - remember too

much is as bad as too little. Investigate

pipe system and trapping.
Best method to pump down to see

if oil can be encouraged back. If

no oil still, drain compressor and

measure in correct quantity.

Expansion valve stuck in open position

(abnormally cold suction Iine).

Ensure bulb is tight on suction and

superheat is correct (normally 5 to 6°C).
Replace power assembly or

valve as necessary.

Damaged or worn compressor

bearing (excessive knocking).

Replace compressor.

Head pressure too high.

Condenser coil clogged or dirty.

Clean condenser coil.

Air or other non-condensable

gas in system.

Evacuate system and re-charge

with new refrigerant.

Overcharge of refrigerant.

Always install new drier

before evacuating.
Reclaim excess refrigerant

from system (liquid only).

Head pressure controller faulty.

Check fan speed controller

- if faulty - replace.

Fan not operating or operating inefficiently.

Check motor - if faulty - replace.

Head pressure too low.

Fan operating too fast in low

ambient conditions.

Check fan speed controller

adjustment - if faulty - replace.

Compressor short cycles or

LP cut-out operated.

Dirty filters.

Replace.

Dirty or icing evaporator (reduced airflow).

Defrost and/or clean. Check gas

charge and expansion valve.

Lack of refrigerant (bubbles in

sight glass only as indication).

Check for leaks - repair and

recharge system.

Clogged filter drier (pressure /

temperature drop across it).

Replace.

Condenser fan running at full

speed in winter (full airflow).

Check fan speed controller

setting - if faulty - replace.

Start up problems in very low ambients.

Check for low suction pressures on

start-up and fit a low ambient start

kit if required, or check operation

of system if already fitted.