Suction throttle valve (stv) (optional extra), Humidifier (optional extra), Easicool™ ezre precision air conditioning – Airedale EasiCool 6kW 64kW User Manual

Page 24: Tr ou ble sh oo tin g, Troubleshooting

Advertising
background image

24

EasiCool EZRE Operational Manual 7610207 V1.0.0_02_2013

Tr

ou

ble

sh

oo

tin

g

EasiCool™ EZRE

Precision Air Conditioning

Troubleshooting

Suction Throttle Valve (STV) (Optional Extra)

FAULT

POSSIBLE CAUSE

REMEDY / ACTION

Suction pressure too low.

Suction throttle valve fully shut.

Check valve opens fully at 100% cooling

demand. Inspect, clean or replace.

High discharge temperature.

Suction throttle valve in operation.

Check suction throttle valve

operation. Inspect, clean or replace.

Open suction throttle valve to

reduce discharge temperature.

Large or complete loss of

refrigerant charge.

Investigate for refrigerant leaks,

repair and re-charge system.

High compressor superheat.

Suction throttle valve shut.

Check suction throttle valve operation.

Inspect, clean or replace.

Large or complete loss of

refrigerant charge.

Investigate for refrigerant leaks,

repair and re-charge system.

Cooling output insufficient.

Suction throttle valve in operation.

Check supply air setpoint and

unit cooling demand.

Hot Gas Re-Heat (HGRH) (Optional Extra)

FAULT

POSSIBLE CAUSE

REMEDY / ACTION

Cooling output insufficient.

Hot gas re-heat coil in operation.

Check cooling demand and ensure

hot gas re-heat valve is closed.
Check hot gas re-heat valve operation.

Inspect, clean or replace.

Re-heat output insufficient.

Faulty hot gas re-heat valve.

Check hot has re-heat valve operation.

Inspect, clean or replace.

Humidifier (Optional Extra)

FAULT

POSSIBLE CAUSE

REMEDY / ACTION

Main fuses / MCB trips when

initially switched on.

Cylinder damage (shorted electrode(s).

Test with Megger - Replace cylinder.

Humidifier ‘called for’ but not filling.

Water not available at cylinder.

Check all mains cold water valves.

Check any strainers fitted.
Check inlet solenoid valve (yellow)

strainer - clean as necessary.
Inlet water solenoid not operating

- check for feed. Replace solenoid

/ control board as necessary.
Mains water pressure over 8 Bar

- fit pressure reducing device.

The humidifier loads with water

but does not produce steam.

Too high steam delivery back pressures.

Check steam delivery pipe is

not blocked with debris.

Cylinder inlet filter clogged.

Clean the filter.

Limescale inside the supply tank.

Clean the supply tank.

Drain solenoid valve faulty.

Check 24 Vac anomalous presence

on the drain solenoid valve and/or

replacement of drain solenoid valve.

The humidifier wets the underlying floor.

Supply or overflow hydraulic circuit leaking. Check the entire hydraulic circuit.
Steam delivery pipe not properly

fastened to the cylinder.

Check fastening of the clamp

on the steam delivery pipe.

Cylinder operating - Low

Current / Low output.

Humidifier in start-up phase.

Wait for impurity concentration to build

up through natural drain cycle. This will

allow an increase in passed current.

Cylinder nearing end of useful life.

Strip and clean or replace.