EasiCool™ EZRE

Precision Air Conditioning

Alarm 52: Phase Failure

When the phase failure is detected, the unit will shut down and the alarm will be indicated on the display and circuit 1

and 2 alarm relays. The alarm will auto reset when alarm condition is cleared. The unit will restart after the delay on

period has elapsed

Alarm 53: Warning Cylinder 1 Maintenance

This alarm indicates that the cylinder operating hours have exceeded. The warning can be reset by the operation hour’s

counter.

Alarm 54: Alarm Cylinder 1 Maintenance

This alarm indicates that the cylinder maximum operating life has been exceeded and the bottle needs replacing.

Alarm 55: Warning Compressor 1 High Discharge Temperature

This alarm is a warning that indicates the discharge temperature sensor is close to the high discharge temperature limit.

This alarm is manual reset and can be cleared by referring to resetting the Alarm

Alarm 56: Compressor 1 High Discharge Temperature

This alarm indicates that the discharge temperature sensor has exceeded the high discharge temperature limit. This

alarm is manual reset and can be cleared by referring to resetting the Alarm

Alarm 57: Warning Compressor 1 Low Discharge Temperature

This alarm is a warning that indicates the discharge temperature sensor is close to the low discharge temperature limit.

This alarm is manual reset and can be cleared by referring to resetting the Alarm

Alarm 58: Compressor 1 Low Discharge Temperature

This alarm indicates that the discharge temperature sensor has exceeded the low discharge temperature limit. This

alarm is manual reset and can be cleared by referring to resetting the Alarm

Alarm 59: Warning Compressor 2 High Discharge Temperature

This alarm is a warning that indicates the discharge temperature sensor is close to the high discharge temperature limit.

This alarm is manual reset and can be cleared by referring to resetting the Alarm

Alarm 60 Compressor 2 High Discharge Temperature

This alarm indicates that the discharge temperature sensor has exceeded the high discharge temperature limit. This

alarm is manual reset and can be cleared by referring to resetting the Alarm

Alarm 61: Warning Compressor 2 Low Discharge Temperature

This alarm is a warning that indicates the discharge temperature sensor is close to the low discharge temperature limit.

This alarm is manual reset and can be cleared by referring to resetting the Alarm

Alarm 62: Compressor 2 Low Discharge Temperature

This alarm indicates that the discharge temperature sensor has exceeded the low discharge temperature limit. This

alarm is manual reset and can be cleared by referring to resetting the Alarm

Alarm 63: Driver 1 LAN Disconnected

This alarm indicates that the system cannot detect a connection to EEV driver 1.

Alarm 64: Bottle Change Alarm

This alarm indicates that the cylinder needs to be changed when a vapac humidifier is selected.

Alarm 65: Unit Switched Off By Display

This alarm indicates that the unit is turned off by the display, the unit can be turned on in the programming section of the

controller.

Alarm 66: Maintenance Required (Mn)

The Mn alarm occurs when the life timer within the CPY board is greater than 1.5 times the user’s maintenance life time.