Installation data, Lifting, Blucube ™ condensing unit – Airedale BluCube 10-48kW User Manual

Page 16

Advertising
background image





BluCube

Condensing Unit

16

Condensing Units

Technical Manual : 7206188 V1.6.0_07 2014

Installation Data

Lifting

Whenever a condensing unit is lifted, it should be from the base and, where possible, with
all packing and protection in position. If slings are used care should be taken to ensure
that the slings do not crush the casework or coil. The slings are to be located into the
recess within the unit frame to ensure safe lifting.

Due note should also be made of the fact that the compressor is at one end of the unit,
and therefore the centre of gravity will also be towards that end.

If the unit is dropped, it should immediately be checked for damage.

Employ lifting specialists.

Local codes and regulations relating to the lifting of this type of equipment should
be observed.

Use the appropriate spreader bars/lifting slings with the holes/lugs provided.
Chains/slings MUST NOT interfere with the casing of fan assembly to avoid damage.

Lift the unit slowly and evenly.

IMPORTANT

If the unit is dropped, it should immediately be checked for damage
and reported to Airedale.

CAUTION

Only use lifting points provided.

Ensure drip tray is removed before lifting (Heat Pump units only)








Minimum lifting chain
length of 1500mm

Sling Length 4500mm